8.7
/ 10
HIGH
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
Description
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
Basic Information
ID
CVE-2025-9041
Source
Rockwell
Published
Aug 14, 2025 at 14:17
Affected Product
Vendor
Rockwell Automation
Product
FLEX 5000 I/O
Version
Version 2.011 or below
Affected Versions
Rockwell Automation FLEX 5000 I/O Version 2.011 or below